R430 Memory Slots

R430 Memory SlotsR430 memory slots gamesSlots
Memory
Environmental specifications

NOTE: For additional information about environmental measurements for specific system configurations, see dell.com/environmental_datasheets.
Temperature
Storage –40°C to 65°C (–40°F to 149°F)
Continuous operation (for altitude less than 950 m or 3117 ft)10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Fresh airFor information on fresh air, see Expanded Operating Temperature section.
Maximum temperature gradient (operating and storage)20°C/h (36°F/h)
Relative humidity
Storage5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
Operating10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Maximum vibration
Operating0.26 G

rms

at 5 Hz to 350 Hz (all operation orientations).
Storage1.88 G

rms

at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock
OperatingSix consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms.
StorageSix consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum altitude
Operating

3048

2000

m (

10,000

6560

ft).
Storage12,000 m (39,370 ft).
Operating temperature de-rating
Up to 35 °C (95 °F)Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.
Air filtration
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
NOTE: Applies to data center and non-data center environments.
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
Corrosive dust
NOTE: Applies to data center and non-data center environments.
  • Air must be free of corrosive dust.
  • Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
Gaseous contamination

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate<200 Å/month as defined by AHSRAE TC9.9.

R430 Memory Slots App

One optional vFlash memory card NOTE: The card slot is available for use only if the iDRAC8 Enterprise license is installed on your system. Front: USB: Two 4-pin, USB 2.0-compliant: Video: 15-pin VGA: Internal: USB: One 9-pin, USB 3.0-compliant: Internal Dual SD Module (IDSDM) Two optional flash memory card slots with the internal SD module. Upgrading a Poweredge R430 to 32GB of RAM. The server documentation will tell you what slots and what size RAM you need to get to where you want to be. Memory specifications The PowerEdge R440 system supports 16 DDR4 registered DIMMs (RDIMMs) slots. Supported memory bus frequencies are 2666 MT/s, 2400 MT/s, 2133 MT/s, and 1866 MT/s. Memory specifications Memory module sockets Memory capacity Minimum RAM Maximum RAM Twelve 288-pin. 8 GB, 16 GB, or 32 GB single rank or dual rank (RDIMMs).